EasyManua.ls Logo

TECO L510S Series - Group 04- Analog signal inputs; Analogue output functions

TECO L510S Series
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-15
Group 04- Analo
g
si
g
nal inputs/ Analo
g
ue output functions
No. Description Range
Factory
Setting
Unit Note
04-00
AVI/ACI analog Input
signal type select
ACI
AVI
0 -
0
0~10V 0~20mA
1
0~10V 4~20mA
2
2~10V 0~20mA
3
2~10V 4~20mA
04-01
AVI Signal Verification
Scan rate
1~200 50 2ms
04-02
AVI Gain 0~1000 100 % *1
04-03
AVI Bias 0~100 0 % *1
04-04
AVI Bias Selection 0: Positive 1: Negative 0 - *1
04-05
AVI Slope 0: Positive 1: Negative 0 - *1
04-06
ACI Signal Verification
Scan rate
1~200 50 2ms
04-07
ACI Gain 0~1000 100 % *1
04-08
ACIBias 0~100 0 % *1
04-09
ACI Bias Selection 0: Positive 1: Negative 0 - *1
04-10
ACI Slope 0: Positive 1: Negative 0 - *1
04-11
Analog Output mode
(AO)
0: Output Frequency
1: Frequency Command
2: Output Voltage
3: DC Bus Voltage
4: Motor Current
0 - *1
04-12
Analog Output AO Gain
(%)
0~1000 100 % *1
04-13
Analog Output AO Bias
(%)
0~1000 0 % *1
04-14
AO Bias Selection
0: Positive
1: Negative
0 - *1
04-15
AO Slope
0: Positive
1: Negative
0 - *1
04-16
Potentiometer Gain on
Keypad
0~1000 100 % *1
04-17
Potentiometer Bias on
Keypad
0~100 0 % *1
04-18
Potentiometer Bias
Selection on Keypad
0: Positive
1: Negative
0 - *1
04-19
Potentiometer Slop on
Keypad
0: Positive
1: Negative
0 - *1

Table of Contents

Other manuals for TECO L510S Series

Related product manuals