4-35
01- 01 v/f Maximum voltage
Range
200:【170.0~264.0】V
400:【323.0~528.0】V
01- 02 Maximum Frequency (base frequency)
Range 【0.2~ 599.00】Hz
01- 03 Maximum Frequency Voltage Ratio
Range 【0.0 ~ 100.0】%
01- 04 Medium Frequency 2
Range 【0.1~599.00】Hz
01- 05 Medium Frequency Voltage Ratio 2
Range 【0.0 ~ 100.0】%
01- 06 Medium Frequency 1
Range 【0.1~599.00】Hz
01- 07 Medium Frequency Voltage Ratio 1
Range 【0.0 ~ 100.0】%
01- 08 Minimum Frequency
Range 【0.1~599.00】Hz
01- 09 Minimum Frequency Voltage Ratio
Range 【0.0 ~ 100.0】%
Max output frequency depends on parameter 01-00, for 01-00=7,It can be set by parameter 01-
02.
For 01-00 ≠7, the maximum output frequency depends on parameter 00-12.
01-10 Volts/Hz Curve Modification (Torque Boost)
Range 【0 ~ 10.0】%
Inverter output V / F curve settings for points B, C can be adjusted by parameter 01-10 to
improve the output torque.
Calculation of B, C point voltage: B point voltage = Xb × maximum output voltage, C point
voltage = Xc × maximum output voltage (Xb, Xc see Page 4-26). When 01-10 = 0, the torque
improvement is disabled.
100
B
C
1 2.5/3.0 50/60
(V)%
Hz
01-10
01-11 V/F start Frequency
Range
【0.00 ~10.00】Hz
VF Start Frequency is for occasion where Start Frequency higher than zero Hz is needed.