4-37
02- Motor parameter
roup
02- 00 Motor no load current. (For slip compensation calculation)
Range
----
02- 01 Motor Rated Current
Range
----
02- 02 Slip Compensation Gain. (V/f mode only)
Range
【0.0 ~ 100.0】(%)
When the load causes the actual motor speed to be reduced below the speed set by
inverter output frequency (Slip) , parameter 02-02 Slip compensation can be used to correct
the speed.
Slip compensation calculation in V/F mode:
Motor slip = Motor synchronous speed- Motor Rated Speed
(02-02)approximate Value=
Motor synchronization speed-Rated speed
Motor synchronization speed
※Note: Parameters 02- 00/02- 01 have to be set according to the specific motor data and in
relation to the Inverter rating model parameter (13- 00).
02- 03 Motor Rated Speed
Range
----
Slide compensation limit, inverter will calculate the motor slide according to 02-03. V/F slide
compensation will not be higher than 02-03.
Note: Please set the value according to motor’s nameplate.
02- 04 Motor Rated Voltage
Range
----
In order to prevent the output voltage of inverter is too high. The output voltage value will
not be higher than 02-04. 02-04 can be changed during operation.
Note: Please set the value according to motor’s nameplate.
02- 05
Motor Rated Power
Range
【0~22.0】kW
02- 06
Motor Rated Frequency
Range
【0~599.0】Hz
02- 07 Motor Auto Tuning
Range
【0】: Disable
【1】: Static auto tuning