4-40
03- External di
ital inputs & Rela
Output functions
03- 00 Multifunction Input Term. S1
03- 01 Multifunction Input Term. S2
03- 02 Multifunction Input Term. S3
03- 03 Multifunction Input Term. S4
03- 04 Multifunction Input Term. S5
Range
【0】:Forward/Stop Command------------(Parameters 00- 02/00-03=1 & 00-04)
【1】:Reverse/Stop Command------------(Parameters 00-02/00-03=1 & 00-04)
【2】:Preset Speed 1 (5- 02)----------------(Parameter Group5)
【3】:Preset Speed 2 (5- 03)----------------(Parameter Group5)
【4】:Preset Speed 4 (5- 05) ---------------(Parameter Group5)
【6】:JOG Forward Command-------------(Parameters 00-18~00-20)
【7】:JOG Reverse Command-------------(Parameters 00-18~00-20)
【8】:Up Command--------------------------- (Parameters 00- 05/00- 06=4& 03-06/03-07)
【9】:Down Command----------------------- (Parameters 00- 05/00- 06=4& 03-06/03-07)
【10】: 2
nd
Acc/Dec times
【11】: Disable Acc/Dec
【12】: Main/ Alternative run source Select-----------------(Parameters 00- 02/00- 03)
【13】: Main/Alternative Frequency Command Select----(Parameters 00- 05/00- 06)
【14】: Rapid Stop (controlled deceleration stop)
【15】: Base Block (
Coast to stop)
【16】: Disable PID Function.------------------(Parameter Goup10)
【17】: Reset
【18】: Enable Auto Run Mode----------------(Parameter Group 6)
【19】: Forced Frequency Run----------------(Parameter Group 14)
【20】: Switch to Constant Pressure 2----------------(Parameter Group 14)
Various example settings and descriptions for Parameters 03-00 to 03-04 are noted in the
following pages seconds from 1 to 13.
1) For setting parameters 03- 00~03- 04 to【0, 1】External Run/Stop Control, refer to 00- 04.
2-wire method. Mode 1.
Example: FWD/STOP and REV/STOP from two inputs ( S1&S2)
Set 00- 04=【0】, S1: 03- 00=【0】(FWD/STOP) , S2: 03- 01=【1】(REV/STOP);
S1
S2
COM
(FWD/STOP)
(REV/STOP)