N3 Drive Operations Manual
A (Advanced) Parameter Details; A092 A097 Cont. 63
NOTE: Refer to the example tables and figures below for additional information
Hz
V
60
30
0
0
5
10
(0mA)
(20mA)
100%
050%
000%
Bias
Upper frequency limit
(b005 = 60.0)
Fig. a
Hz
V
60
30
0
0
5
10
(0mA)
(20mA)
100%
050%
000%
Bias
Upper frequency limit
(b005 = 60.0)
Fig. b
A
B
C
D
A92 A93 A94 A95 A97
A 100% 050% 000 000 100%
B 100% 000% 000 000 100%
a. setting
A92 A93 A94 A95 A97
C 100% 050% 000 001 100%
D 100% 000% 000 001 100%
b. setting
Fig. 19.16
Hz
V
60
30
0
2
10
(4mA)
(20mA)
- 100%
- 050%
- 000%
Bias
Upper frequency limit
(b005 = 60.0)
Fig. c
E
A92 A93 A94 A95 A97
E 100% 020% 001 000 100%
c. setting
V
60
30
0
5
10
(20mA)
- 100%
- 050%
- 000%
Bias
Upper frequency limit
(b005 = 60.0)
Fig. d
F
Hz
A92 A93 A94 A95 A97
F 100% 020% 001 001 100%
d. setting
Fig. 19.17
4.)The inverter reads the average value of the A/D signals once per (A096×4ms). Set the scan intervals to
minimize the environmental noise by increasing the value of A096. However, increasing the scan time will result
in a decreased the response time.