4-17
Group
Auto Run function group
Code Parameter Name Setting Range Default
Unit
Attribute
13-00
Auto Run( sequencer) mode
selection
0: Disabled.
1: Single cycle.(Continues to run from the
Unfinished step if restarted).
2: Periodic cycle. (Continues to run from the
unfinished step if restarted).
3: Single cycle, then holds the speed Of final
step to run. (Continues to run from the
unfinished step if restarted).
4: Single cycle. (Starts a new cycle if restarted).
5: Periodic cycle. (Starts a new cycle if
restarted).
6: Single cycle, then hold the speed of final
step to run. (Starts a new cycle if restarted).
0
13-01
Auto _ Run Mode Frequency Command 1
0.00~400.00
0.00
Hz *1
13-02
Auto _ Run Mode Frequency Command 2
13-03
Auto _ Run Mode Frequency Command 3
13-04
Auto _ Run Mode Frequency Command 4
13-05
Auto _ Run Mode Frequency Command 5
13-06
Auto _ Run Mode Frequency Command 6
13-07
Auto _ Run Mode Frequency Command 7
13-08~13-15 Reserved
13-16
Auto_ Run Mode Running Time Setting 0
0.0~3600.0
0.0
Sec
*1
13-17
Auto_ Run Mode Running Time Setting 1
13-18
Auto_ Run Mode Running Time Setting 2
13-19
Auto_ Run Mode Running Time Setting 3
13-20
Auto_ Run Mode Running Time Setting 4
13-21
Auto_ Run Mode Running Time Setting 5
13-22
Auto_ Run Mode Running Time Setting 6
13-23
Auto_ Run Mode Running Time Setting 7
13-24~13-31 Reserved
13-32
Auto_ Run Mode Running Direction 0
0: stop
1: forward
2: reverse
0
13-33
Auto_ Run Mode Running Direction 1
13-34
Auto_ Run Mode Running Direction 2
13-35
Auto_ Run Mode Running Direction 3
13-36
Auto_ Run Mode Running Direction 4
13-37
Auto_ Run Mode Running Direction 5
13-38
Auto_ Run Mode Running Direction 6
13-39
Auto_ Run Mode Running Direction 7