Description
51 Function Code Error
52 Address Error
53 Data Amount Error
54 DATA Over Range
55 Writing Mode Error
4. Inverter Control
4.1Command Data (Readable and Writable)
Register No.
Content
2500/A000H
Reserved
2501/A001H
Operation Signal
Bit
Description 1 0
0 Operation Command Run Stop
1 Reverse Command Reverse Forward
2 Reserved
3 Fault Reset Reset
4 Jog Command Jog
5 Reserved
6 Multi-function Command S1 ON OFF
7 Multi-function Command S2 ON OFF
8 Multi-function Command S3 ON OFF
9 Multi-function Command S4 ON OFF
A Multi-function Command S5 ON OFF
B Reserved
C Multi-function Command R1A ON OFF
D Reserved
E Reserved
F Reserved
2502/A002H
Frequency Command
2503/A003H
Reserved
2504/A004H
Reserved
2505/A005H
Reserved
2506/A006H
Reserved
2507/A007H
Reserved
2508/A008H
Reserved
2509/A009H
Reserved
Note: Write in zero for Not used BIT, do not write in data for the reserved register.