6-71
(3) READ (read the program from the PM05 program spare cartridge to SG2 (RAM))
READ
YES
>NO
When C type or K type machine power up, the program in PM05 will be auto downloaded to the machine
and be executed. But there are same exceptional cases:
1. program about 20 point in PM05 can’t be downloaded to 10 point machine;
2. program about DC type in PM05 can’t be downloaded to AC type machine;
3. program about Transistor type in PM05 can’t be downloaded to Relay type machine;
(1) ∼ (3) Now Press:
↑ ↓
Move the cursor
OK Execute the instruction, then back to main menu
ESC Back to main menu
(4) SET (system setting)
ID SET 01
Æ
ID setting (00~99)
REMOTE I / 0 N
Æ
Remote I/O Mode (N: none M: Master S:S lave)
BACK LIGHT ×
Æ
Back light mode (√: always light ×: light for 5s after pressed.)
M KEEP √
Æ
M: non-Volatile (
√:Volatile ×: Non- Volatile)
I/O NUMBER 0
Æ
Expansion I/O Points(0~3)
I/O ALARM √
Æ
Siren setting when is not available to Expansion I/O Points (√:Yes
×:No)
C KEEP ×
Æ
in stop/run switching, Counter Present Value Keeping(√:Yes ×:No)
Note:
M KEEP function is only available for keeping M status in RUN mode when power is resupplied after loss.
Now Press:
↑ ↓ ← →
Move the cursor
SEL Begin to edit.
Press ‘SEL’
and ‘←
→’
Move the cursor for ‘ID SET item’