EasyManua.ls Logo

TECSYSTEM NT935 WS EVO - 3 Technical Specifications

TECSYSTEM NT935 WS EVO
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
NT935 WS EVO
TECHNICAL SPECIFICATIONS
NT935 WS EVO
POWER SUPPLY
Supply rated values
85-260 Vac-Vdc
50/60HZ
Vdc with invertible polarities
INPUTS
4 inputs for three-wire Pt100 RTD sensors (max section 1.5mm²)
Connections on removable terminal boards
Input channels protected against electromagnetic interference
Thermoresistances cable compensations
500m (1mm²)
OUTPUTS
2 alarm relays (ALARM AND TRIP) SPDT
1 sensor or operating failure (FAULT) relay SPST
2 ventilation management relays (FAN 1 and FAN 2) SPST
Output relays with 10A-250Vca-res COSФ=1 contacts
Wi-Fi Connection: protocol 802.11 b/g/n, frequency 2.4 GHz with removable external antenna
Max 100m
in open field
DIMENSIONS
100 x 100 mm DIN 43700 prof. 150 mm (including antenna - installed at 90°C - and terminal
board)
Hole 92 x 92 mm
TESTS AND PERFORMANCE
Construction in compliance with the EC - RED regulations
Protection from electrical interferences EN 61000-4-4
Dielectric strength 1500 Vac for a min. between output relays and sensors, relays and power
supply, power supply and sensors
Accuracy ±1% full scale value, ±1 digit
Ambient operating temperature from 20°C to +60°C
Permitted humidity 90% without condensate
Polycarbonate frontal film IP65
Housing NORYL 94 _V0
Absorption 7.5VA

Related product manuals