Vdc with invertible polarities
4 inputs for three-wire Pt100 RTD sensors (max section 1.5mm²)
Connections on removable terminal boards
Input channels protected against electromagnetic interference
Thermoresistances cable compensations
2 alarm relays (ALARM AND TRIP) SPDT
1 sensor or operating failure (FAULT) relay SPST
2 ventilation management relays (FAN 1 and FAN 2) SPST
Output relays with 10A-250Vca-res COSФ=1 contacts
Wi-Fi Connection: protocol 802.11 b/g/n, frequency 2.4 GHz with removable external antenna
100 x 100 mm DIN 43700 prof. 150 mm (including antenna - installed at 90°C - and terminal
board)
Construction in compliance with the EC - RED regulations
Protection from electrical interferences EN 61000-4-4
Dielectric strength 1500 Vac for a min. between output relays and sensors, relays and power
supply, power supply and sensors
Accuracy ±1% full scale value, ±1 digit
Ambient operating temperature from –20°C to +60°C
Permitted humidity 90% without condensate
Polycarbonate frontal film IP65