Installation and Programming Manual - СА62 Alarm Control Panel 31
ADDRESS 2012 - ZONE 1 ATTRIBUTES 2
Zone 1
Attributes 2
Parameters "ATTRIBUTES 2" for ZONE 1 are programmed at this address.
More than one attribute can be assigned for the zone. Pressing a digital button with the respective
number will activate a given attribute. Every activated attribute number is indicated as a lighting on
LED or enclosed in brackets number. Pressing the same digital button again will deactivate the at-
tribute. At the end of this procedure, the LEDs or zone numbers, which correspond to the assigned
attributes only, will remain activated.
The parameters “ATTRIBUTES 2” are as follows:
1. Bell Delay
The siren will be activated when the set Bell Delay time is over.
The Bell Delay time can be programmed at ADDRESS 4013 (for Partition A) and at ADDRESS 4023
(for Partition B).
2. Silent
This attribute is valid only for zones type Panic (at ADDRESS 2хх0 is set type 5). In arming mode, the
siren will not be activated if the Silent (silent panic) attribute is assigned. The programmable PANIC
type outputs and the system communicator will be activated only. A violation of a zone is indicated with
a ashing LED or enclosed in brackets zone number while the zone is active.
3. Video On
Armed
Video recording of alarm events
In case of alarm event the VIDEO ON ARMED outputs will be activated for 1 minute.
4. Write to
LOG
Write to LOG le
Every zone activation and restoring, irrespective of the system arming status, will be recorded in the
system LOG le. The attribute “Write to log” concerns the events OPEN (zone activation) and CLOSE
(zone restoring). This attribute is valid for all type of zones except the zones TAMPER type. If the zone
is set with TAMPER type (at ADDRESS 2хх0 is set type 6) the programming of this attribute has no
matter.
5. Chime
“CHIME” Mode
In disarmed mode and assigned "Chime" attribute, with every activation of a zone the keyboards will
produce a specic sound signal.
Default settings
- no attribute is set
ADDRESS 2013 - ZONE 1 ATTRIBUTES 3
Zone 1
Attributes 3
At this address are assigned only parameters "ATTRIBUTES 3" for Key-Switch type zone.
More than one attribute can be assigned for the zone. Pressing a digital button with the respective
number will activate a given attribute. Every activated attribute number is indicated as a lighting on
LED or enclosed in brackets number. Pressing the same digital button again will deactivate the at-
tribute. At the end of this procedure, the LEDs or zone numbers, which correspond to the assigned
attributes only, will remain activated.
The parameters “ATTRIBUTES 3” are as follows:
1. Pulse /
Latch
24-hout Key-Switch type zone.
With assigned Pulse attribute every impulse will change alter-
natively the arming status of the system - respectively armed/ dis-
armed.
With assigned Latch attribute, if the zone is activated - the parti-
tion* is armed, if the zone is in normal operating status - the parti-
tion* is disarmed.
*The partition to which the zone is attached.
Attention: If the zone is attached to the both partitions in the sys-
tem, its reaction will depend on the current partitions status. In the
SUPPLEMENT D are shown detailed algorithms for the partitions
reaction with Key-Switch type zone.
Attribute
Indication
LED LCD
Pulse
1
Latch
(1)
2. Full /Stay
This attribute determinates the arming type - FULL ARM or STAY
ARM.
Attribute
Indication
LED LCD
Full Arm
2
Stay Arm
(2)
3. Disarm
Enable
This attribute determinates whether the zone will disarm the sys-
tem (DISARM ENABLED) or not (DISARM DISABLED).
Attribute
Indication
LED LCD
Disabled
3
Enabled
(3)
Default settings
- Disarm Enable attribute