28
IP.HIGH:BATT /MESSAGE (During mains high alarm operate from batteries or not selection)
OPTION DESCRIPTION
BATT During A65 mains high alarm, UPS starts operating from batteries (for protection)
MESSAGE During A65 mains high alarm, UPS shows only message
In some cases, if the mains input voltage is high (adjustable level), it is better to operate on batteries to prevent
any possible damage to the UPS.. But this selection can cause battery discharge if the mains input voltage is
continuously high. This function is selectable from adjust menu.
Optional dry contact AUX relays function selection from ADJUST MENU
Two auxiliary relays are available with selectable functions from the adjust menu. The selectable functions are
as follows:
Message Function
Relay activates on any alarm
Relay activates if battery voltage is out of tolerance
Relay activates if output voltage is out of tolerance
Relay activates if input voltage is out of tolerance
Relay activates if load is transferred to bypass
Relay activates if input voltage is restored
Relay activates if load is greater than 100%
Relay activates if battery test is being performed
Relay activates if cabinet inside temperature is high
Relay activates if battery fuse is off or blown
Relay activates if battery test fails
Relay activates if boost charge is active
Relay activates if the output voltage is zero
Relay activates if inverter failure alarm occurs
Relay activates if shutdown is applied
Relay activates if any fault occurs
Some other features in adjust menu:
Mains voltage low alarm level Adjustable
Mains voltage OK level Adjustable
Mains voltage high alarm level Adjustable
Bypass input voltage high warning level Adjustable
Bypass input voltage low warning level Adjustable
Battery voltage high alarm level Adjustable
Battery voltage low warning level Adjustable
Battery voltage shutdown level Adjustable
Battery test failed voltage level Adjustable
Cabinet temperature high alarm level Adjustable
Output voltage high alarm level Adjustable
Output voltage low alarm level Adjustable
Battery charge current Adjustable
Battery quantity selection Adjustable
Frequency synchron band Adjustable
Boost charge time Adjustable
Voltage range selection 220-230 volts AC selectable