32
BATTERI
ES
Total number of battery blocks 20 nominal (battery number selectable)
Internal batteries 20x12V/12Ah
Float Charge Voltage (adjustable) 272 V (for 20x12V batteries at 25 C)
End of Discharge Voltage (adjustable) 192 V (for 20x12V batteries)
Boost Charge Available
Boost charge voltage (adjustable) 288 V (for 20x12V batteries)
Battery Test Available (automatic or manual)
Max. recharging current (adjustable) 3.0 A DC (independent of the o/p load)
Average battery high protection standard
Cold start from batteries standard
Battery temperature compansiation standard
INTERFACE
RS 232 comm. Port Standard
RS 485 comm. Port OPTIONAL
Remote Monitoring Panel OPTIONAL
SNMP Adaptor OPTIONAL
Modbus Adaptor OPTIONAL
Alarm Relay Contacts 3x standard (+ 2xprogrammable relay optional)
Alarm relay NO/NC selection standard
REPO Input Standard (NO/NC selectable)
Remote monitoring panel OPTIONAL
E
NVIRONMENT
Operating Temperature 0-40 C
Operating Humidity <90% non-condensing
Max. İnstallation altitude 2000m at nominal power
Acoustic Noise <50 dB
Dimensions (WxDxH) (mm) 215 x 775 x 585 mm
Protection Class IP20
Weight (Without Batteries) 41 kgs