MP-3000 Controller
126
99 USDA 1 Sensor Open Circuit
(Check Alarm)
• Occurs during pre-trip (PTI) test only.
• Container ID starts with MAE, MSF or MWC.
• Temperature below -50 C (-58 F).
• Indicates:
• All 3 USDA sensors are missing
• Defective cable No. 3
• Check USDA sensors and sensor
connections.
• Check cable No. 3 between controller and
relay board.
112 Zero Current Too High
(Check Alarm)
• Ground (zero current) circuit is 30 milliamps.
• Indicates:
• Defective motor or heater insulation to ground
• Enter Manual Function Test menu and test
(operate) each motor and heater separately.
Note when alarm occurs.
115 Probe Error
(Check Alarm)
• Occurs during pre-trip (PTI) test or probe test failed
in Chilled mode.
• Temperature difference between return air and
evaporator coil sensors is too high (1.5 C [2.7 F]
difference maximum)
•
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
2,000 ohms at 25 C (77 F).
116 Probe Error
(Check Alarm)
• Occurs during pre-trip (PTI) test or probe test failed
in Chilled mode.
• Temperature difference between return air and
supply air sensors is too high (0.8 C [1.5 F]
difference maximum)
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must be
2,000 ohms at 25 C (77 F).
117 Probe Error
(Check Alarm)
• Occurs during pre-trip (PTI) test or probe test failed
in Chilled mode.
• Temperature difference between LH supply and RH
supply sensors is too high (0.5 C [1.0 F] difference
maximum)
• Check sensor connections. Check sensor
resistance of each sensor. Resistance must
be 2,000 ohms at 25 C (77 F).
• Check left hand and right hand supply air
sensor locations.
118 High Refrigerant Level (Check Alarm)
• Detects overcharge of refrigerant
• Correct overcharged refrigerant level
Alarm Codes, Descriptions and Corrective Actions (Continued)
Code Description Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermo King CSR Series and is the answer not in the manual?

Thermo King CSR Series Specifications

General IconGeneral
BrandThermo King
ModelCSR Series
CategoryRefrigerator
LanguageEnglish

Related product manuals