EasyManua.ls Logo

Toptech FCM II - Wiring Examples for RTD Temperature Probes

Toptech FCM II
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
FCM II Installation Guide: 20160419 - Part # 2307
3.2.4 RTD TEMPERATURE PROBE WIRING
White
4-Wire
100 Ohm Platium RTD
Alpha = 0.0385
Note: All 4 wires MUST be run to the
sensor. Do not simply jumper REF- to
COM or REF+ to V+ at the FCM II.
For 3-wire and 2 wire probes, the
connection of REF- to COM and REF+ to
V+ should be as close as possible to the
probe (within inches).
White
Red
Red
White
Red
2-Wire RTD Connection
White
Red
3-Wire RTD Connection
Red
Com R- R+ V+
D4 D3 D2 D1
RTD
Top Side
Bottom Row
NC NC I- I+
E4 E3 E2 E1
Top Side
Middle Row
4-20 mA IN
Iout Rtn Com V+
F4 F3 F2 F1
Top Side
Top Row
4-20 mA OUT
E
D
F
Terminal
Number
1234
1 2 3 4
1234
Figure 3.5 FCM II Field Wiring: RTD