- I/O_expX-inX alarm: Activates if the specific expansion programmable input on the specific expansion board is
activated and triggered.
- Battery1-2 Overvoltage: Activates if the voltage of the specific battery is higher than the specified overvoltage set
point.
- I/O Diesel Communication Error: Activates if no communication with the diesel I/O board could be established for
15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1 minute the controller will
reboot to try and fix the problem.
- I/O Expansion Communication Error: Activates if no communication with the Expansion I/O board could be
established for 15 seconds.
- Communication System Failure: Activates when the communication task has stopped responding. This alarm
condition is critical and will be followed by a controller reboot to try and fix the problem.
- File System Failure: Activates when a file system error is detected. This alarm condition is critical and will be
followed by a controller reboot to try and fix the problem.