EasyManuals Logo

Tornatech HFD User Manual

Tornatech HFD
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20
- I/O_expX-inX alarm: Activates if the specific expansion programmable input on the specific expansion board is
activated and triggered.
- Battery1-2 Overvoltage: Activates if the voltage of the specific battery is higher than the specified overvoltage set
point.
- I/O Diesel Communication Error: Activates if no communication with the diesel I/O board could be established for
15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1 minute the controller will
reboot to try and fix the problem.
- I/O Expansion Communication Error: Activates if no communication with the Expansion I/O board could be
established for 15 seconds.
- Communication System Failure: Activates when the communication task has stopped responding. This alarm
condition is critical and will be followed by a controller reboot to try and fix the problem.
- File System Failure: Activates when a file system error is detected. This alarm condition is critical and will be
followed by a controller reboot to try and fix the problem.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tornatech HFD and is the answer not in the manual?

Tornatech HFD Specifications

General IconGeneral
BrandTornatech
ModelHFD
CategoryController
LanguageEnglish

Related product manuals