27
If Enabled, this timer will delay the "Fail When Running Alarm".
- Local Request Detection:
This is the delay it will take to the controller to detect a Local start of the pump.
The other timers are self explanatory and set the time delay on alarms.
Inputs/Outputs Configuration
Config > Advanced > IO Diesel Input Selection -
Config - Output Config
This page, if logged in, allows the re-assignation of 3 programmable inputs by pressing on the signal name. If the
Deluge Valve signal is selected, it will be assigned as a normally closed input. Proceed with caution as this may
cause the engine to start. If an alarm signal is chosen, it can be configured on the next page (Enabled, NO/NC,
Audible, Importance (Alarm or Warning). The available signals are:
- Low Fuel Level, High Fuel Level, Fuel Tank Leak
- Water Reservoir Empty, Water Reservoir Low, Water Reservoir High
- Flow Meter ON, Main Relief Valve Open
- Low Suction Pressure
- Lockout
- Remote Manual Start
- Deluge Valve Start (NC)