EasyManuals Logo

Tornatech HFD User Manual

Tornatech HFD
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
If Enabled, this timer will delay the "Fail When Running Alarm".
- Local Request Detection:
This is the delay it will take to the controller to detect a Local start of the pump.
The other timers are self explanatory and set the time delay on alarms.
Inputs/Outputs Configuration
Config > Advanced > IO Diesel Input Selection -
Config - Output Config
This page, if logged in, allows the re-assignation of 3 programmable inputs by pressing on the signal name. If the
Deluge Valve signal is selected, it will be assigned as a normally closed input. Proceed with caution as this may
cause the engine to start. If an alarm signal is chosen, it can be configured on the next page (Enabled, NO/NC,
Audible, Importance (Alarm or Warning). The available signals are:
- Low Fuel Level, High Fuel Level, Fuel Tank Leak
- Water Reservoir Empty, Water Reservoir Low, Water Reservoir High
- Flow Meter ON, Main Relief Valve Open
- Low Suction Pressure
- Lockout
- Remote Manual Start
- Deluge Valve Start (NC)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tornatech HFD and is the answer not in the manual?

Tornatech HFD Specifications

General IconGeneral
BrandTornatech
ModelHFD
CategoryController
LanguageEnglish

Related product manuals