Toshiba HFCR407C - [D1] Master Outdoor Unit Set-Up Alarm

Toshiba HFCR407C
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106
14
Check interface PC board.
Set only one unit as master, turn off all
power source, and then restart the operation.
No
Are there multiple inverter
outdoor units connected ?
Set only one inverter outdoor unit
per system.
Yes
No
Is set-up of the master outdoor
units position duplicated ?
[Set SW08 bit 2 on interface PC
board of each unit.(*1)]
Yes
Troubleshooting
Diagnostic procedure for check code
Check code Operation cause
[d1] 1. No. of connected inverter outdoor units
Master outdoor unit set-up alarm 2. Incorrect set-up of master outdoor unit
3. Defective outdoor interface PC board
( *1) Set-up of outdoor unit at center position (SW08 bit 2 set-up on outdoor interface PC board)
OFF: Slave/ON: Master (Automatic set-up for inverter outdoor unit).