Control circuit configuration
Indoor units
(4) Switch positions at shipment from the factory
Switch No. Function Description Position at shipment
from factory
SW01 Indoor unit No. Group operation control set-up
Set-up 1: Master unit
2 to 16: Slave units
SW02 Network address set-up
For contents of address set-up, see the next page.
SW03 TA adjust
No. 1 ON Normal
No. 2 OFF Normal
SW06 Ceiling height
No. 1 OFF Normal
No. 2 OFF Normal
When height of ceiling exceeds 2.7 m set No. 1 to ON.
SW07 Central control
switching ON Communication error
(Non relay)
OFF (Normal)
Communication OK
No. 2 OFF Normal
SW08 Indoor HP set-up Factory set
For contents of switch set-up, see section (5)
ON Address set-up by remote controller is
unavailable.
OFF Address set-up by remote controller is
available.
No. 7
No. 1
13