70
12
Self diagnostic display information
Outdoor units
(5) Outdoor unit information data display (Displayed on inverter unit only)
SW03 SW02 SW01 Displayed content
1 to 3 1 to 16 4 Indoor communication/ A [01] to [48]: Indoor address number
receive status B [1]: Receiving, [- -]: No connection
5 Indoor check code A [01] to [48]: Indoor address number
B [—]: No error, a check code is displayed when an error occurs
6 Indoor horse power A [01] to [48]: Indoor address number
B Corresponded HP is displayed. ([--]: No connection)
[0,8], [1], [1,2], [1,5], [1,7], [2],
[2,5], [3], [3,2], [4], [5]
7 Indoor demand command (S code) A [01] to [48]: Indoor address number
B [0] In STOP time, [3] to [F]: During operation (S3 to SF)
8 Indoor PMV opening A [01] to [48]: Indoor address number
B Data is displayed as pulse
9 Indoor saturation temperature A [01] to [48]: Indoor address number
B Data is displayed as temperature
10 Indoor TA sensor A [01] to [48]: Indoor address number
B Data is displayed as temperature
11 Indoor TC2 sensor A [01] to [48]: Indoor address number
B Data is displayed as temperature
12 Indoor TC1 sensor A [01] to [48]: Indoor address number
B Data is displayed as temperature
NOTE: The indoor address number is set by selecting SW02 or SW03
SW03 SW02 Outdoor unit number 7 segment display A
1 1 to 16 SW02 set-up number [01] to [16]
2 1 to 16 SW02 set-up number + 16 [17] to [32]
3 1 to 16 SW02 set-up number + 32 [33] to [48]
• 7 segment display A, B
Display A
Display B
D716 D717
D714
D715