4
Parts specifications
Indoor units
2-way cassette: MM-TU056
No. PARTS NAME TYPE SPECIFICATIONS
1 Fan motor PAF-230-7-4 Output (rated) 7 W, 4 pole, 230 V, 1 phase, 50 Hz
2 Running capacitor – Fan motor EEP2H105HQA105 AC 500 V, 1 μF
3 Pulse motor valve EDM-B40YPTR-7B-A Capacity: 40
2-way cassette: MM-TU042
No. PARTS NAME TYPE SPECIFICATIONS
1 Fan motor PAF-230-7-4 Output (rated) 7 W, 4 pole, 230 V, 1 phase, 50 Hz
2 Running capacitor – Fan motor EVM45M504UF AC 500 V, 1 μF
3 Pulse motor valve EDM-B25YPTF-7B-A Capacity: 25
2-way cassette: MM-TU028
No. PARTS NAME TYPE SPECIFICATIONS
1 Fan motor PAF-230-7-4 Output (rated) 7 W, 4 pole, 230 V, 1 phase, 50 Hz
2 Running capacitor – Fan motor EEP2H105HQA105 AC 500 V, 1 μF
3 Pulse motor valve EDM-B25YPTF-7B-A Capacity: 25
2-way cassette: MM-TU056, MM-TU042, MM-TU028
No. PARTS NAME TYPE SPECIFICATIONS
4 Transformer TT - 03 - 1 DC 16.3 V – 0.5 A / AC 11.6 V – 0.15 A
5 Pulse motor EDM-MD12TF-3 DC 12 V
6 Pressure sensor 150/100NH6-D Power voltage DC 12 V
7 Sensor for room temperature TA Maximum input: °C 25 50
38 mA at 25 °C kΩ 10 3.45
8 Sensor for heat exchanger Tc1 Maximum input: °C -12 0 25 50
34 mA at 25 °C kΩ 62.3 32.8 10 3.6
9 Sensor for heat exchanger Tc2 Maximum input: °C 0 25 50
26 mA at 25 °C kΩ 34.6 10 3.4
10 Control PCB CM**C01 AC 220 – 240 V
11 Power PCB P**RC01 AC 220 – 240 V

Table of Contents