Chapter 5 RAS Information
6F8C1872
5.3 PF612A information that can be referenced as I/O
connection
Table 5-20 Information that can be referenced as I/O connection
Address
15
0
0000h
PF module status (1W)
0001h
Healthy counter (1W)
The address is the offset address (word address) from the beginning of the PF612 interface
memory
.
(1)
PF module status
Indicates the status of the modules installed on the local unit.
Table 5-21 PF module status
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
0000h
ONL
PF_MODE
NPR
ONL (ONLINE)
1 : PF module is online 0: Not online
PF_MODE (PF_MODE)
00: PF module is online
01: PF module is standby
10: PF module is not operating
11: PF module is down
NPR (NO_PARA)
1: No activation request 0: Activation request
(2)
Healthy counter
Indicates the normal operating status of the PF module.
Table 5-22 Healthy counter
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
0001h
Healthy Counter
Indicates that the PF module is operating normally. A 16-bit counter that is updated every
100 ms.
Returns to 0 after FFFFh.