Appendix A Specifications
6F8C1872
A.1 General Specifications
Table A-1 General Specifications
Operating ambient temperature
0 to 55°C, 24-hour average temperature 40°C or less
Operating ambient relative
humidity
10 to 95%RH, level RH2 (no condensation)
Dust 0.3mg/m
3
(no conductive dust)
2 (usually, no conductive contamination) or less
No corrosive gasses
No silicon-containing substances
Up to 2000m above sea level
Vibration resistance
(vibration immunity)
IEC 60068-2-6, Test Fc-compliant
5 f < 8.4Hz : Half amplitude 3.5mm
8.4 f < 150Hz : Constant acceleration 9.8m/sec
2
Shock resistance
(shock immunity)
IEC 60068-2-27, test Ea-compliant
147m/s
2
(15G) X, Y, Z direction, 3 cycles each
Shipping package: 1,000mm
Product package: 300mm
I/O power supply, Signal line
4kV (contact discharge), level ESD-3
Inside of indoor control panel
(Note 1)
For long-term storage, store spare parts in dark places and avoid hot or wet places.
For long-term storage, the temperature and humidity should be 0-40°C and 20-80%RH (no condensation)
respectively, and the temperature variation rate should be less than or equal to 10°C/h.
(Note 2)
The following components shall not be contained
Hydrogen sulfide, sulfurous acid gas, chlorine gas, nitrogen oxides (NOx), sulfur oxides (SOx), ammonia,
silicon gas, and so on.
(Note 3)
Grounding (e.g., mesh grounding) other than Class D grounding can be applied to the system under a
condition which achieves the equivalent effect as with Class D grounding. For grounding other than Class D,