Unified Controller nv series type1 light PROFIBUS-DP Module PF611A / PF612A User’s Manual
19
3.4 Registration and Setup
This chapter describes the registration and setup method when connecting PROFIBUS to
an type1 light controller. The Engineering tool (Ver. 4.11 or later) is used for registration and
setup.
Registration and Setup Procedure
Registration and Setup procedure is as follows.
In order to register and setup PF611A / PF612A, you must create folders for the target
systems, stations, and controllers.
Start registration and setup
(1) Register PF611A / PF612A module in the hardware configuration in the
station folder.
(2) Register the LAN to be used (PROFIBUS-DP in this case) in system
configuration.
(3) Register the area to be used in the controller interface DPRAM of the PF
module as transmission block.
(4) For each transmission block, set the network variable name to the
transmission data.
End
Figure 3-3 PF611A / PF612A registration and setup procedure
(*) The PF611A node No. and transmission parameters are set by HMS configurator.
The PF612A parameters are set with module switches.
(*) The GSD files (TSB1177.GSD : PF611A / TSB1178.GSD : PF612A) are attached to
Engineering tool Version 4.14.16 or later.
Refer to Appendix C "Registration and Setup Procedure" for details.