Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 81
Preset Speed 1
Program Frequency Preset Speeds
Up to fifteen (15) output frequency values that fall within the
Lower-Limit and the Upper-Limit range may be programmed into
the ASD and output as a Preset Speed. A properly configured
preset speed is assigned a frequency that will be output from the
ASD by selecting the preset speed (1 – 15) using a binary selec-
tion process.
The preset speed to be run is selected by applying a binary value
(0001 – 1111) at the S1 – S4 discrete input terminals.
This parameter assigns an output frequency to binary number
0001 (Preset Speed 1). The binary selection number 0001 is
applied to S1 – S4 of the Terminal Board to output Preset Speed
1.
Perform the following setup to allow the system to receive Preset
Speed control input at the S1 – S4 terminals:
1. Program Fundamental Standard Mode Selection
Command Mode Selection Terminal Board.
2.Program Terminal Input Terminals S1 (set to Preset
Speed (Bit) 1; LSB of 4-bit count).
Note: Though the ASD display shows the selections as Preset
Speed 1, 2, 3, and 4; the selections are preset speed binary
bits 1, 2, 3, and 4 (i.e., binary nibble 1111).
3.Repeat for S2 – S4 (MSB of 4-bit count) as Preset Speed Bit 2
– 4, respectively (all Normally Open).
4.Program Frequency Preset Speeds Preset Speed1
(set an output frequency as Preset Speed 1; repeat for Preset
Speeds 2 – 15 as required).
5.Place the system in the Remote mode (Local/Remote LED
Off).
6.Provide a Run command (connect F and/or R to CC).
Connect S1 to CC to run Preset Speed 1 (S1 to CC = 0001
binary).
With S1 – S4 configured to output Preset Speeds (F115 – F118),
0001 – 1111 may be applied to S1 – S4 of the Terminal Board to
run the associated Preset Speed.
If bidirectional operation is required, F and R must be connected
to CC.
With S1 being the least significant bit of a binary count, the S1 –
S4 settings will produce the programmed speed settings as indi-
cated in the Preset Speed Truth Table to the right.
Direct Access Number —
F018
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-
Limit Freq. (F012)
Units — Hz
Preset Speed 1
Preset Speed Truth Table
Bit 4 Bit 3 Bit 2 Bit 1
Preset
S4
MSB
S3 S2
S1
LSB
Output
1 0 0 0 1 F018
2 0 0 1 0 F019
3 0 0 1 1 F020
4 0 1 0 0 F021
5 0 1 0 1 F022
6 0 1 1 0 F023
7 0 1 1 1 F024
8 1 0 0 0 F287
9 1 0 0 1 F288
10 1 0 1 0 F289
11 1 0 1 1 F290
12 1 1 0 0 F291
13 1 1 0 1 F292
14 1 1 1 0 F293
15 1 1 1 1 F294
Note: 1 = Terminal connected to CC.
F018 – F019