42
Monitor Function
(1) Display of system Information (Displayed on Header Outdoor Unit Only)
liatedyalpsiD30WS20WS10WS
1
1
3
Unused A B
2
System capacity A […8]~[
64
]:8 to
64
HP
B [HP]
3
No. of outdoor units A […1]~[…
3
]:1 to
3
B […P]
4
No. of indoor units connected / No.
of units with cooling
thermostat
ON
A […0.]~[
64
.]:0 to
64
(No. of units connected)
B [C…0]~[C
64
]:0 to
64
(No. of units with cooling
thermostat
ON)
5
No. of indoor units connected / No.
of units with heating
thermostat
ON
A […0.]~[
64
.]:0 to
64
(No. of
units connected)
B [H…0]~[H
64
]:0 to
64
(No. of units with heating
thermostat
ON)
6
Amount of compressor command
correction
A Value displayed in hexadecimal format
B
7
Release control A Normal: [r. …], During release control: [r.1]
B –
8
Oil equalization control Normal: [oiL-0]
During oil equalization control: [oiL-1]
9
Oil equalization request A Displayed through LED segment lighting pattern
B
10
Refrigerant/oil recove
ry operation A Oil recovery in cooling: [C1], Normal: [C …]
B Refrigerant recovery in heating: [H1], Normal: [H …]
11
Automatic addressing A [Ad]
B During automatic addressing: [… FF], Normal: [… … …]
12
Power peak-cut A [dU]
B Normal: [… … …], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
13
BAsutatslortnoclanoitposyalpsiD)tupnidraob.C.P(lortnoclanoitpO
Operation mode
selection: During priority heating (normal) h.
. . . .
.cgniloocytiroirP
. . . .
.HylnognitaeH
. . . .
.CylnognilooC
. . . .
Priority given to No. of indoor units in operation n.
. . . .
.UtinuroodnicificepsotnevigytiroirP
. . .
.
External master ON/OFF: Normal
.…. . . .
Start input
.1. . . .
Stop input
.0. . . .
Night operation: Normal
. . …. . .
Start input
. . 1. . .
Snowfall operation: Normal
. . .…. .
Start input
. . .1. .
14
Optional control
(BUS line input)
Same as above
15
Unused
16
–A–
B –
F G
A
D
U2U1 U3 U4
Dp
B
E C
Display section A Display section B
Outdoor unit No.
If element F shown on sketch at left turned on:
Header unit oil equalization request
If element C shown on sketch at left turned on:
Follower unit oil equalization request