43
Monitor Function
(2) Display of Outdoor Unit Information (Displayed on each Outdoor Unit)
liatedyalpsiD30WS20WS10WS
1
1
1
Outdoor unit No.: [U1] to [U3]A
Check code
B Check code (only latest one displayed)
If there is no check code, [– – –] is displayed.
If there is sub-code, check code [
] and sub-code [– ] are displayed
alternately, for 3 s econds and 1 second, respectively.
<SW04> push SW function: Fan operation at outdoor unit with check code. 7-segment display section A: [E.1]
<SW04 + SW05> push SW function: Fan operation at outdoor unit without check code.
7-segment display section A: [E.0]
<SW05> push SW function: Fan operation function check mode is cancelled.
2
–A–
B –
3
O
peration mode A Stop [… …]
Normal cooling: [… C], Normal heating: [… H], Normal defrosting: [… J]
B –
4
Outdoor unit HP capacity A
8HP: [… 8], 10HP: [… 10], 12HP: [… 12],
14HP: [14], 16HP: [16] , 18HP: [18], 20HP: [20], 22HP: [22]
B […HP]
5
Compressor operation command * Operation data of each compressor is displayed in turn in 2 second intervals.
Normal: Compressor speed (rps) is displayed in decimal format.
7-segment display (A/B): [C1. ... ... ... ] [ ... , ] [C2. ... ... ... ] [... , ]
<SW04> push SW function: Switches to display of operating current (decimal value).
7-segment display (A/B): [i1. ] [i2. ]
Pressing of <SW05> restores normal display.
6
Outdoor fan mode A [FP]
B Mode 0 to 63: [… 0] to [63]
7
Compressor backup A [C.b.]
B
Displays compressor backup setting status
Normal: [… … …]
Compressor No. 1 backup: [1 … …]
Compressor No. 2 backup: [ … 1 …]
8
–A–
B –
9
Control valve output data Displays co
ntrol output status of solenoid valve A B
………1.HFFO:2evlavyaw-4/NO:evlavyaw-4
………0.HNO:2evlavyaw-4/FFO:evlavyaw-4
10
001….2
SV2: ON / SV51: OFF / SV52: OFF
010….2SV2: OFF / SV51: ON / SV52: ON
100….2SV2: OFF / SV51: OFF / SV52: ON
11
SV3A: ON / SV3B: OFF / SV3C: OFF / SV3D: OFF 3. 1 0 0 0
SV3A: OFF / SV3B: ON / SV3C: OFF / SV3D: OFF 3. 0 1 0 0
SV3A: OFF / SV3B: OFF / SV3C: ON / SV3D: OFF 3. 0 0 1 0
SV3A: OFF / SV3B: OFF
/ SV3C: OFF / SV3D: ON 3. 0 0 0 1
12
001….4
SV41: ON / SV42: OFF
010….4SV41: OFF / SV42: ON
100….4
SV41: OFF / SV42: OFF
13 PMV1/PMV3 opening Displays opening data in decimal format
. P
…tamroflamicedniatadgnineposyalpsiDgninepo4VMP
14
. P
15
Oil level judgment status
].Lo[AlamroN
B
Initial display: [… … …], Oil level judgment result: [#. .$]
Displayed letters #, and $ represent judgment results for compressor Nos.
1 and 2, respectively (“0” for normal and “1” or “2” for low level).
<SW04> push SW function: Displays low level confirmed judgment result of each compressor.
* Pressing of <SW05> restores
normal display.
A [L d.]
B
Compressor No. 1 low level being confirmed: [L … …]
Compr
essor No. 2 low level being confirmed: [… L …]
SV2, SV51, SV52
PMV4
PMV1/PMV3 ,