5
Refrigerant Piping
Lc
Lb
La
LA
L3
L4
L5
L6
f
g
h
i
j
a b c d e
(j)
L7
Height
difference
between
outdoor
units
H3 ≤ 5 m
Outdoor unit
A
Header
unit
B
Follower
unit
C
Follower unit
Outdoor unit connecting pipes
Outdoor unit connection piping kit
(For linking of outdoor units)
The longest piping between outdoor units:
LO ≤ 25 m
Main piping L1
Height
difference
between
outdoor
and indoor
units:
H1 ≤ 70 m
First branching
section
Branching header
Y-shaped branching
joint
Indoo
r unit connecting
pipe
Indoor unit
The longest piping length: L ≤ 235 m
The longest piping length from the
first branch: Li
≤ 90 m
Y-shaped
branching joint
Indoor unit
Height
difference
between
indoor
units:
H2 ≤ 40 m
stinu 3 ot pUnoitanibmoc tinu roodtuO
Note
(*1):(D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch.
(*2) :If the height difference (H1) between indoor and outdoor unit exceeds 3 m, set 65 m or less.
(*3) :If the max. combined outdoor unit capacity is 54HP or more, then max. equivalent length is 70 m or less (real length is 50 m or less).
(*4) :If the height difference (H2) between indoor units exceeds 3 m, set 50 m or less.
PH 06 ot pUstinu roodtuo fo yticapac latoT
stinu 46 ot pUnoitcennoc tinu roodnI
Total capacity of indoor units
(varies depending on the height difference between
indoor units.)
H2 ≤ 15m 135% of outdoor units’ capacity
15m < H2 105% of outdoor units’ capacity
<Cooling,Heat pump type>
For T8P - E
Allowable length of refrigerant pipes and allowable height difference between units
System restriction