An example of the connection of
the open collector OUT (sink logic)
An example of the connection of
the relay output terminals
ï‚· Output terminal setting
Default outputs low-speed signal (ON signal) to RY-RC terminal. This setting must be changed to invert
the polarity of the signal.
[Parameter setting]
Title Function Adjustment range Default setting
f130
Output terminal selection 1A (RY-RC)
0-255
(Refer to section 11.7)
4: LOW (Low-
speed detection
signal)
Setting value 5 is reverse signal.
Note) Set f132 to output to FLA-FLC-FLB terminals and f131 to OUT terminal.
6.1.2 Output of designated frequency reach signal
f102 : Speed reach detection band
ï‚· Function
When the output frequency becomes equal to the setting by designated frequency  f102, an ON
or OFF signal is generated.
[Parameter setting]
â– Parameter setting of designated frequency and detection band
Title Function Adjustment range Default setting
f102 Speed reach detection band 0.0-fh (Hz) 2.5
â– Parameter setting of output terminal selection
Title Function Adjustment range Default setting
f131
Output terminal
selection 2A (OUT)
0-255
(Refer to section 11.7.)
6: RCH (Output frequency attainment signal
(acceleration/deceleration completed))
Setting value 7 is reverse signal.
Note: Set f132 to output to FLA-FLC-FLB terminals and f130 to RY-RC terminal.
+24V
RY
RC
Ry
+24V
OUT
NO
CC
Ry
P24