E6581697
K-13
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0363 Integral gain - 0.01/0.01 0.01-100.0 0.20 6.20
0366 Differential gain - 0.01/0.01 0.00-2.55 0.00
0367 Process upper
limit
Hz 0.1/0.01 0.0- *1
0368 Process lower
limit
Hz 0.1/0.01 0.0- 0.0
0369 PID control
feedback signal
selection
- - 0: Disabled
1: VIA
2: VIB
3: VIC
4 to 6: -
0
0372 Process
increasing rate
(speed type PID
control)
s 0.1/0.1 0.1-600.0 10.0
0373 Process
decreasing rate
(speed type PID
control)
s 0.1/0.1 0.1-600.0 10.0
0375 Factory specific
coefficient 3B
- - - -
* 3
0376 Factory specific
coefficient 3C
- - - -
0378 Number of pulse
train input
pps 1/1 100-5000 250 6.6.5
0380 PID
forward/reverse
characteristics
selection
- - 0: Forward
1: Reverse
0 6.20
0382
Hit and stop
control
- -
0: Disabled
1: Enabled
2: -
0
6.18.2
0383 Hit and stop
control frequency
Hz 0.1/0.01
0.1-30.0 5.0
0384 Factory specific
coefficient 3D
- - - -
* 3
0385 Factory specific
coefficient 3E
- - - -
0386 Factory specific
coefficient 3F
- - - -
0389 PID control
reference signal
selection
- -
0: fmod/f207 selected
1: Terminal board VIA
2: Terminal board VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
0
6.20
0390 Factory specific
coefficient 3G
- - - -
* 3
0391 Hysteresis for
lower-limit
frequency
operation
Hz 0.1/0.01 0.0-ul 0.2 6.9.1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.