E6581697
K-14
11
Torque boost parameters 1
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0: Auto-tuning disabled
1: Initialization of  (after
execution : 0)
2: Auto-tuning executed
(after execution: 0)
3: -
4: Motor constant auto calculation
(after execution: 0)

0400 Auto-tuning - -
5: 4+2 (after execution: 0)
0 6.21

0401 Slip frequency
gain
% 1/1 0-150 50

0402 Automatic torque
boost value
% 0.1/0.1 0.1-30.0 * 2

0405 Motor rated
capacity
kW 0.01/0.01 0.01-22.00 * 2

0412 Motor specific
coefficient 1
- - - - * 4

0415 Motor rated
current
A 0.1/0.1 0.1-100.0 * 2 6.21

0416 Motor no-load
current
% 1/1 10-90 * 2

0417 Motor rated
speed
min-1 1/1 100-64000 *1

0441 Power running
torque limit 1 level
% 1/0.01 0-249%,
250:Disabled
250 6.22.1

0443 Regenerative
braking torque
limit 1 level
% 1/0.01 0-249%,
250:Disabled
250

0444 Power running
torque limit 2 level
% 1/0.01 0-249%,
250:Disabled
250

0445 Regenerative
braking torque
limit 2 level
% 1/0.01 0-249%,
250:Disabled
250

0451 Acceleration/decel
eration operation
after torque limit
- 1/1
0: In sync with acceleration /
deceleration
1: In sync with min. time
0 6.22.2

0452 Power running
stall continuous
trip detection time
s
0.01/0.01
0.00-10.00
0.00 6.22.3

0454 Constant output
zone torque limit
selection
- -
0:Constant output limit
1:Constant torque limit
0 6.22.1

0458 Motor specific
coefficient 2
- - - - * 4

0459 Load inertia
moment ratio
Times 0.1/0.1 0.1-100.0 1.0 6.21

0460 Motor specific
coefficient 3
- - - - * 4

0461 Motor specific
coefficient 4
- - - -

0462 Motor specific
coefficient 5
- - - -

0467 Motor specific
coefficient 6
- - - -
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*4: Motor specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.