E6581697
D-10
4
4.3.2 Return to default settings
: Default setting
Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title Function Adjustment range Default setting
Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10, 11: -
12: Number of starting clear
13: Default setting 2 (complete
initialization)
0
+ This function will be displayed as 0 during reading on the right. This previous setting is displayed.
Example:
+ cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (=)
Setting to sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency () :50Hz Upper limit frequency () :50Hz
Base frequency 1 () :50Hz Base frequency 2 () :50Hz
VIA input point 2 frequency ()
:50Hz VIB input point 2 frequency ():50Hz
VIC input point 2 frequency () :50Hz Automatic light-load high-speed operation
Process upper limit () :50Hz frequency () :50Hz
Motor rated RPM ()
:1410 min
-1
Communication command point 2 frequency
() :50Hz