Unit Start Up
138 RT-SVX36K-EN
Figure 99. 50 ton high efficiency operating pressure curve (all compressors and condenser fans “On”)
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Discharge Pressure, PSIG
Sucon Pressure, PSIG
95
FAmbient
Figure 100. 50 ton eFlex variable speed - circuit 1 only operating pressure curve (compressor at 100% and all condenser
fans “On”). See Figure 97, p. 137 for circuit 2 operating pressures.
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Discharge Pressure, PSIG
Sucon Pressure, PSIG
95
FAmbient