Installation
66 RT-SVX36K-EN
Occupied/Unoccupied output - De-energized
(Occupied)
VO Relay - Energized
Pre-heater State - Off (if equipped)
VOM Mode “B” Priority2-Pressurize:
Supply fan - ON
VFD - 100% (if equipped)
Exhaust/Return fan - OFF, Exhaust/Return dampers
- Closed
O/A dampers - Open
Heat - All stages OFF, Modulating Heat output at 0
VDC
Occupied/Unoccupied output - Energized
(Unoccupied)
VO Relay - Energized
Pre-heater State - Off (if equipped)
VOM Mode “C” Priority 3 - Exhaust/Return:
Supply fan - OFF
VFD - 0% (if equipped)
Exhaust/Return fan - ON, Exhaust/Return dampers -
Open
O/A dampers - Closed
Heat - All stages OFF, Modulating Heat output at 0
VDC
Occupied/Unoccupied output - De-energized
(Occupied)
VO Relay - Energized
Pre-heater State - Off (if equipped)
VOM Mode “D” Priority4-Purge:
Supply fan - ON
VFD - 100% (if equipped)
Exhaust/Return fan - ON, Exhaust/Return dampers -
Open
O/A dampers - Open
Heat - All stages OFF, Modulating Heat output at 0
VDC
Occupied/Unoccupied output - Energized
(Unoccupied)
VO Relay - Energized
Pre-heater State - Off (if equipped)
VOM Mode “E” Priority5-Purge with duct pressure
control:
Supply fan - ON
VFD - (if equipped) Controlled by S/A Pressure
Control with supply air pressure high limit disabled.
Exhaust/Return fan - ON, Exhaust/Return dampers -
Open
O/A dampers - Open
Heat - All stages OFF, Modulating Heat output at 0
VDC
Occupied/Unoccupied output - Energized
(Unoccupied)
VO Relay - Energized
Pre-heater State - Off (if equipped)
OFF” - will appear in theVentilation Override screen after
all VOM binary inputs have been reset (opened).
Due to codes in some areas, the definitions for some or all
of theVOM modes may have to be lock ed into the program
by the user. Once the definitions are locked, theVentilation
Override Module must be replaced in order to reprogram
that sequence.
Refer to Figure 40, p. 57 or Figure 47, p. 75 for the proper
connection terminals in the unit control panel for each of
the VOM initiating device’s and the appropriate
Programming,Troubleshooting Guide (PTG Latest
Edition) for programming instructions.
Emergency Override Definitions (with LCI-I/
BCI-I module installed)
When an LCI-I/BCI-I module is installed, the user can
initiate one of five (5) Emergency Override sequences that
have the following predefined unit operation:
PRESSURIZE
Supply Fan - On
Exhaust/Return Fan - Off (if equipped)
Exhaust/Return Dampers - Closed (if equipped)
OA Dampers - Open
Heat - All heat stages Off (staged gas and elec.),
Hydronic
Heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - Energized
VO Relay - Energized (with VOM module installed)
OA Preheater State - Off (with VCM module
installed)
DEPRESSURIZE
Supply Fan - Off
Exhaust/Return Fan - On (if equipped)
Exhaust/Return Dampers -Open (if equipped)
OA Dampers - Closed
Heat - All heat stages Off (staged gas and elec.),
Hydronic
Heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
OA Preheater State - Off (with VCM module
installed)

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals