Unit Start Up
98 RT-SVX36K-EN
Notes:
1. Compressors for the 20 thru 30 Ton units can operate individually or together and in any order while in the SERVICE TEST mode.
2. Compressors 1A &1B and compressors 2A & 2B operate simultaneously within their respective circuits on the 40 thru 75 Ton units. There is no 1B compressor for variable speed.
3. Condenser fan outputs can operate individually or together and in any order while in the SERVICE TEST mode.
4. Once the unit has started, refer to the Status Menu in the Human Interface for the OA CFM.
5. RTM OCC/UNOCC output in the Service Test Mode must be in the unoccupied mode to open the system VAV boxes or to drive the VFD to 100%.
IMPORTANT: Do not operate the compressors without the supply and condenser fans; low suction or high head pressure will develop and compressor
damage may occur.
40 - 60 Ton
1A ON OFF OFF
1A-Off/1B-On
OFF OFF OFF K11-On K3-Off K12-Off K4-Off
2A-Off/2B-Off
1B ON OFF OFF
1A-On/1B-Off
OFF OFF OFF K11-On K3-Off K12-On K4-Off
2A-Off/2B-Off
2A ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-Off K3-On K12-Off K4-Off
2A-Off/2B-On
2B ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-Off K3-On K12-Off K4-On
2A-On/2B-Off
70 - 90Ton
1A ON OFF OFF
1A-Off/1B-On
OFF OFF OFF K11-On K3-Off K12-Off K4-Off
2A-Off/2B-Off
1B ON OFF OFF
1A-On/1B-Off
OFF OFF OFF K11-On K3-Off K12-On K4-Off
2A-Off/2B-Off
2A ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-Off K3-On K12-Off K4-Off
2A-Off/2B-On
2B ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-Off K3-On K12-Off K4-On
2A-On/2B-Off
105 - 130 Ton
1A ON OFF OFF
1A-Off/1B-On
OFF OFF OFF K11-Off K3-On K12-Off K4-Off
2A-Off/2B-Off
1B ON OFF OFF
1A-On/1B-Off
OFF OFF OFF K11-Off K3-On K12-Off K4-On
2A-Off/2B-Off
2A ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-On K3-Off K12-Off K4-Off
2A-Off/2B-On
2B ON OFF OFF
1A-Off/1B-Off
OFF OFF OFF K11-On K3-Off K12-On K4-Off
2A-On/2B-Off
Table 42. Service test guide for component operation Part I of II (continued)
Component
Being Tested
COMPONENT CONFIGURATION
Supply
Fan
Return
Fan
Exhaust
Fan
Condenser
Fans
Heat Stages Compressor Stage
1231234

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals