CHILLED WATER UNIT - RADIAL FANS WITH E.C. TECHNOLOGY
Technical characteristics
1) Unit in complete version (including packaging)
2)0060Bunitsavailableonlyinversionswithoutelectricalheaters
3)Nominalairow–Maximumfanpowersupply
4)Minimumairowonlyallowedforunitwithoutelectricalresistances
1) Unit in complete version (including packaging)
2)0060Aunitsavailableonlyinversionswithstandardorimprovedelectricalheaters
3)Nominalairow–Maximumfanpowersupply
4)Minimumairowonlyallowedforunitwithelectricalresistances
Model 0020B 0025B 0030B 0040B 0060B2
Height mm 1740 1740 1740 1740 1740
Width mm 550 550 550 550 850
Depth mm 450 450 450 450 450
Weight1 kg 120 145 145 170 225
Air Flow m
3
/h 1610 2280 2305 3265 4490
E.S.P Maximum 3 Pa 106 53 34 63 20
Minimum air ow m
3
/h 10404 11504 19404 19404 3020
Power supply voltage V/ph/Hz 230/1N/50 230/1N/50 230/1N/50 230/1N/50 230/1N/50
Model 0020A 0025A 0030A 0040A 0060A2
Height mm 1740 1740 1740 1740 1740
Width mm 550 550 550 550 850
Depth mm 450 450 450 450 450
Weight 1 kg 120 145 145 170 225
Air Flow m
3
/h 1610 2280 2305 3265 4490
E.S.P Maximum 3 Pa 106 53 34 63 20
Minimum air ow m
3
/h 10404 21504 21504 21504 3200
Power supply voltage V/ph/Hz 400/3N/50 400/3N/50 400/3N/50 400/3N/50 400/3N/50

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Jupiter JDAC Series and is the answer not in the manual?

Trane Jupiter JDAC Series Specifications

General IconGeneral
BrandTrane
ModelJupiter JDAC Series
CategoryChiller
LanguageEnglish

Related product manuals