EasyManua.ls Logo

Trane TR200 - Page 106

Trane TR200
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[161] Running reverse The output is high when the adjustable frequency drive is running coun-
ter-clockwise (the logical product of the status bits ‘running’ AND ‘re-
verse’).
[165] Local reference active The output is high when par.3-13
Reference Site = [2] Local or when par.
3-13
Reference Site = [0]
Linked to hand auto
at the same time as the
keypad is in [Hand on] mode.
[166] Remote reference active
The output is high when par.3-13
Reference Site [1] or
Linked to hand/
auto
[0] while the keypad is in [Auto on] mode.
[167] Start command active The output is high when there is an active start command (i.e., via digital
input bus connection or [Hand on] or [Auto on], and no stop command
is active.
[168] Drive in hand mode The output is high when the adjustable frequency drive is in Hand on
mode (as indicated by the LED light above [Hand on].
[169] Drive in auto mode The output is high when the adjustable frequency drive is in Hand on
mode (as indicated by the LED light above [Auto on].
[180] Clock Fault The clock function has been reset to default (2000-01-01) because of a
power failure.
[181] Preventive Maintenance One or more of the preventive maintenance events programmed in par.
23-10
Maintenance Item has passed the time for the specified action in
par.23-11
Maintenance Action.
[190] No-Flow A No-Flow situation or Minimum Speed situation has been detected if
enabled in par.22-22
Low Speed Detection.
[191] Dry Pump A dry pump condition has been detected.
[192] End of Curve A pump running with max. speed for a period of time without reaching
the set pressure has been detected. To enable this function, see par.
22-50
End of Curve Function.
[193] Sleep Mode The adjustable frequency drive/system has set to sleep mode. See par.
22-4*.
[194] Broken Belt A broken belt condition has been detected. This function must be ena-
bled in par.22-60
Broken Belt Function.
[195] Bypass Valve Control The bypass valve control (digital/relay output in the adjustable frequency
drive) is used for compressor systems to unload the compressor during
start-up by using a bypass valve. After the start command is given, the
bypass valve will be open until the adjustable frequency drive reaches
par.4-11
Motor Speed Low Limit [RPM]). After the limit has been reached
the bypass valve will be closed, allowing the compressor to operate nor-
mally. This procedure will not be activated again before a new start is
initiated and the adjustable frequency drive speed is zero during the re-
ceiving of start signal. par.1-71
Start Delay can be used in order to delay
the motor start. The bypass valve control principle:
Parameter Description
TR200 Programming Guide 4-69

Table of Contents

Other manuals for Trane TR200

Related product manuals