6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range: Function:
0.07 V* [Application dependant] Sets the analog input scaling value to correspond to the low reference/
feedback value (set in par.6-34
Term. X30/11 Low Ref./Feedb. Value).
6-31 Terminal X30/11 High Voltage
Range: Function:
10.00 V* [Application dependant] Sets the analog input scaling value to correspond to the high reference/
feedback value (set in par.6-35
Term. X30/11 High Ref./Feedb. Value).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range: Function:
0.000 N/
A*
[-999999.999 - 999999.999
N/A]
Sets the analog input scaling value to correspond to the low voltage val-
ue (set in par.6-30
Terminal X30/11 Low Voltage).
6-35 Term. X30/11 High Ref./Feedb. Value
Range: Function:
100.000
N/A*
[-999999.999 - 999999.999
N/A]
Sets the analog input scaling value to correspond to the high voltage
value (set in par.6-31
Terminal X30/11 High Voltage).
6-36 Term. X30/11 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical
noise on terminal X30/11.
par.6-36
Term. X30/11 Filter Time Constant cannot be changed while the
motor is running.
6-37 Term. X30/11 Live Zero
Option: Function:
This parameter makes it possible to disable Live Zero monitoring. For
example, this may be used if the analog outputs are used as part of a
decentral I/O system (e.g., when not part of any adjustable frequency
drive-related control functions, but feeding a building management sys-
tem with data).
[0] * Disabled
[1] * Enabled
TR200 Programming Guide 4-87