6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e., Terminal 42. Analog outputs are
current outputs: 0/4–20 mA. Common terminal (terminal 39) is the same terminal and has the same electrical
potential for analog common and digital common connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option: Function:
Select the function of Terminal 42 as an analog current output. A motor
current of 20 mA corresponds to I
max
.
[0] * No operation
[100] Output freq. 0-100 : 0–100 Hz, (0–20 mA)
[101] Reference Min-Max : Minimum reference - Maximum reference, (0–20 mA)
[102] Feedback +-200% : -200% to +200% of par.20-14
Maximum Reference/Feedb., (0–20 mA)
[103] Motor cur. 0-Imax : 0 - Inverter Max. Current (par.16-37
Inv. Max. Current), (0–20 mA)
[104] Torque 0-Tlim : 0 - Torque limit (par.4-16
Torque Limit Motor Mode), (0–20 mA)
[105] Torque 0-Tnom : 0 - Motor rated torque, (0–20 mA)
[106] Power 0-Pnom : 0 - Motor rated power, (0–20 mA)
[107] * Speed 0-HighLim : 0 - Speed High Limit (par.4-13
Motor Speed High Limit [RPM] and par.
4-14
Motor Speed High Limit [Hz]), (0–20 mA)
[113] Ext. Closed-loop 1 : 0–100%, (0–20 mA)
[114] Ext. Closed-loop 2 : 0–100%, (0–20 mA)
[115] Ext. Closed-loop 3 : 0–100%, (0–20 mA)
[130] Out fr 0-100 4-20 : 0–100 Hz
[131] Reference 4-20mA : Minimum Reference - Maximum Reference
[132] Feedback 4-20mA : -200% to +200% of par.20-14
Maximum Reference/Feedb.
[133] Motor cur. 4-20mA : 0 - Inverter Max. Current (par.16-37
Inv. Max. Current)
[134] Torq.0-lim 4-20mA : 0 - Torque limit (par.4-16
Torque Limit Motor Mode)
[135] Torq.0-nom 4-20mA : 0 - Motor rated torque
[136] Power 4-20mA : 0 - Motor rated power
[137] Speed 4-20mA : 0 - Speed High Limit (4-13 and 4-14)
[139] Bus ctrl. : 0–100%, (0–20 mA)
[140] Bus ctrl. 4-20 mA : 0 - 100%
[141] Bus ctrl t.o. : 0–100%, (0–20 mA)
[142] Bus ctrl 4-20mA t.o. : 0 - 100%
[143] Ext. CL 1 4-20 mA : 0 - 100%
[144] Ext. CL 2 4-20 mA : 0 - 100%
[145] Ext. CL 3 4-20 mA : 0 - 100%
Parameter Description
TR200 Programming Guide 4-89