EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0–10 mA
Output signal 0 or 4 mA is needed at Min ref - set par.6-51
Terminal 42 Output Min Scale to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par.6-52
Terminal 42 Output Max Scale to 200%
(20 mA / 10 mA x 100%=200%).

6-53 Terminal 42 Output Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %]
6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
6-60 Terminal X30/8 Output
Option: Function:
[0] * No operation
[100] Output freq. 0-100
[101] Reference Min-Max
[102] Feedback +-200%
[103] Motor cur. 0-Imax
[104] Torque 0-Tlim
[105] Torque 0-Tnom
[106] Power 0-Pnom
[107] Speed 0-HighLim
[113] Ext. Closed-loop 1
[114] Ext. Closed-loop 2
[115] Ext. Closed-loop 3
[130] Out fr 0-100 4-20
Parameter Description
TR200 Programming Guide 4-91