[40] Drive stopped This event is TRUE if the adjustable frequency drive is stopped or coasted
by any means (either via digital input, serial communication bus or oth-
er).
[41] Reset Trip This event is TRUE if the adjustable frequency drive is tripped (but not
trip-locked) and the reset button is pressed.
[42] Auto Reset Trip This event is TRUE if the adjustable frequency drive is tripped (but not
trip-locked) and an automatic reset is issued.
[43] OK Key This event is TRUE if the OK key on the keypad is pressed.
[44] Reset Key This event is TRUE if the Reset key on the keypad is pressed.
[45] Left Key This event is TRUE if the Left key on the keypad is pressed.
[46] Right Key This event is TRUE if the Right key on the keypad is pressed.
[47] Up Key This event is TRUE if the Up key on the keypad is pressed.
[48] Down Key This event is TRUE if the Down key on the keypad is pressed.
[50] Comparator 4 Use the result of comparator 4 in the logic rule.
[51] Comparator 5 Use the result of comparator 5 in the logic rule.
[60] Logic rule 4 Use the result of logic rule 4 in the logic rule.
[61] Logic rule 5 Use the result of logic rule 5 in the logic rule.
[70] SL Timeout 3 Use the result of timer 3 in the logic rule.
[71] SL Timeout 4 Use the result of timer 4 in the logic rule.
[72] SL Timeout 5 Use the result of timer 5 in the logic rule.
[73] SL Timeout 6 Use the result of timer 6 in the logic rule.
[74] SL Timeout 7 Use the result of timer 7 in the logic rule.
[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
13-03 Reset SLC
Option: Function:
[0] * Do not reset SLC Retains programmed settings in all group 13 parameters (13-*).
[1] Reset SLC Resets all group 13LC-## parameters (13-*) to default settings.
Comparators are used for comparing continuous variables (i.e., output frequency, output current, analog input,
etc.) to fixed preset values. In addition, there are digital values that will be compared to fixed time values. See
explanation in par.13-10
Comparator Operand. Comparators are evaluated once in each scan interval. Use the
result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with an index of
0 to 5. Select index 0 to program Comparator 0, select index 1 to program Comparator 1, etc.
4-108 TR200 Programming Guide