5. Connect to the line power supply.
6. Carry out various tests.
7. The results are displayed on the keypad and the adjustable frequen-
cy drive moves into an infinite loop.
8. par.14-22
Operation Mode is automatically set to normal operation.
Carry out a power cycle to start up in normal operation after a control
card test.
If the test is OK:
keypad readout: Control Card OK.
Disconnect the line power supply and remove the test plug. The green
LED on the control card will light up.
If the test fails:
keypad readout: Control Card I/O failure.
Replace the adjustable frequency drive or control card. The red LED on
the control card is turned on. To test the plugs, connect/group the fol-
lowing terminals as shown below: (18 - 27 - 32), (19 - 29 - 33) and (42 - 53
- 54).
[2] Initialization
Select
Initialization
[2] to reset all parameter values to default settings,
except for par.15-03
Power-ups, par.15-04 Over Temps and par.
15-05
Over Volts. The adjustable frequency drive will reset during the
next power-up.
par.14-22
Operation Mode will also revert to the default setting
Normal
operation
[0].
[3] Boot mode
14-23 Typecode Setting
Option: Function:
Typecode re-writing. Use this parameter to set the typecode matching
the specific adjustable frequency drive.
TR200 Programming Guide 4-125