20-12 Reference/Feedback Unit
Option: Function:
See par.20-02
Feedback 1 Source Unit for details.
20-13 Minimum Reference/Feedb.
Range: Function:
0.000
Proc-
essCtrlU-
nit*
[Application dependant] Enter the desired minimum value for the remote reference when oper-
ating with par.1-00
Configuration Mode set for Closed-loop [3] operation.
Units are set in par.20-12
Reference/Feedback Unit.
Minimum feedback will be -200% of either the value set in par.
20-13
Minimum Reference/Feedb. or in par.20-14 Maximum Reference/
Feedb., which ever numeric value is the highest.
NOTE: If operating with par.1-00
Configuration Mode set for Open-loop [0], par.3-02 Minimum Reference must
be used.
20-14 Maximum Reference/Feedb.
Range: Function:
100.000
Proc-
essCtrlU-
nit*
[Application dependant] Enter the maximum reference/feedback for closed-loop operation. The
setting determines the highest value obtainable by summing all refer-
ence sources for closed-loop operation. The setting determines 100%
feedback in open-loop and closed-loop (total feedback range: -200% to
+200%).
TR200 Programming Guide 4-159