21-15 Ext. 1 Setpoint
Range: Function:
0.000
Ex-
tPID1Un
it*
[-999999.999 - 999999.999
ExtPID1Unit]
The setpoint reference is used in extended 1 closed-loop. Ext.1 Setpoint
is added to the value from the Ext.1 Reference source selected in par.
21-13
Ext. 1 Reference Source.
21-17 Ext. 1 Reference [Unit]
Range: Function:
0.000
Ex-
tPID1Un
it*
[-999999.999 - 999999.999
ExtPID1Unit]
Readout of the reference value for the closed-loop 1 controller.
21-18 Ext. 1 Feedback [Unit]
Range: Function:
0.000
Ex-
tPID1Un
it*
[-999999.999 - 999999.999
ExtPID1Unit]
Readout of the feedback value for the closed-loop 1 controller.
21-19 Ext. 1 Output [%]
Range: Function:
0 %* [0 - 100 %] Readout of the output value for the closed-loop 1 controller.
21-2* Closed-loop 1 PID
Configure the closed-loop 1 PID controller.
21-20 Ext. 1 Normal/Inverse Control
Option: Function:
[0] * Normal
Select
Normal
[0] if the output should be reduced when feedback is higher
than the reference.
[1] Inverse
Select
Inverse
[1] if the output should be increased when feedback is
higher than the reference.
21-21 Ext. 1 Proportional Gain
Range: Function:
0.01 N/
A*
[0.00 - 10.00 N/A]
If (Error x Gain) jumps with a value equal to what is set in par.20-14
Maximum Reference/Feedb., the PID con-
troller will try to change the output speed equal to what is set in par. 4-13/4-14, Motor Speed High Limit, but in
practice of course limited by this setting.
The proportional band (error causing output to change from 0%–100%) can be calculated by means of the for-
mula:
(
1
Proportional
Gain
)
×
(
Max
Reference
)
Parameter Description
TR200 Programming Guide 4-175