21-55 Ext. 3 Setpoint
Range: Function:
0.000
Ex-
tPID3Un
it*
[-999999.999 - 999999.999
ExtPID3Unit]
See par.21-15
Ext. 1 Setpoint for details.
21-57 Ext. 3 Reference [Unit]
Range: Function:
0.000
Ex-
tPID3Un
it*
[-999999.999 - 999999.999
ExtPID3Unit]
See par.21-17
Ext. 1 Reference [Unit] for details.
21-58 Ext. 3 Feedback [Unit]
Range: Function:
0.000
Ex-
tPID3Un
it*
[-999999.999 - 999999.999
ExtPID3Unit]
See par.21-18
Ext. 1 Feedback [Unit] for details.
21-59 Ext. 3 Output [%]
Range: Function:
0 %* [0 - 100 %] See par.21-19
Ext. 1 Output [%] for details.
Configure the closed-loop 3 PID controller.
21-60 Ext. 3 Normal/Inverse Control
Option: Function:
See par.21-20
Ext. 1 Normal/Inverse Control for details.
[0] * Normal
[1] Inverse
21-61 Ext. 3 Proportional Gain
Range: Function:
0.01 N/
A*
[0.00 - 10.00 N/A] See par.21-21
Ext. 1 Proportional Gain for details.
21-62 Ext. 3 Integral Time
Range: Function:
10000.0
0 s*
[0.01 - 10000.00 s] See par.21-22
Ext. 1 Integral Time for details.
21-63 Ext. 3 Differentation Time
Range: Function:
0.00 s* [0.00 - 10.00 s] See par.21-23
Ext. 1 Differentation Time for details.
TR200 Programming Guide 4-183