22-60 Broken Belt Function
Selects the action to be performed if the broken belt condition is detected.
Option: Function:
[0] * OFF
[1] Warning The drive will continue to run, but activate a Broken Belt Warning [W95].
A drive digital output or a serial communication bus can communicate a
warning to other equipment.
[2] Trip The drive will stop running and activate a Broken Belt alarm [A 95]. A
drive digital output or a serial communication bus can communicate an
alarm to other equipment.
NOTE
Do not set par.14-20 Reset Mode to [13] Infinite auto reset when par.22-60 Broken Belt Function is set to [2] Trip. Doing
so will cause the drive to continuously cycle between r
unning and stopping when a broken belt condition is detected.
NOTE
If the drive is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the
drive experiences a persistent alarm condition, be sure to disable the bypass’ automa
tic bypass function, if [2] Trip is
selected as the broken belt function.
22-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Sets the broken belt torque as a percentage of the rated motor torque.
22-62 Broken Belt Delay
Range: Function:
10 s [0 - 600 s] Sets the time for which the broken belt conditions must be active before
carrying out the action selected in par.22-60
Broken Belt Function.
22-7* Short Cycle Protection
When controlling refrigeration compressors, often there will be a need for limiting the numbers of starts. One
way to do this is to ensure a minimum run time (time between a start and a stop) and a minimum interval
between starts.
This means that any normal stop command can be overridden by the
Minimum Run Time
function (par.
22-77
Minimum Run Time) and any normal start command (Start/Jog/Freeze) can be overridden by the
Interval
Between Starts
function (par.22-76 Interval between Starts).
None of the two functions are active if
Hand On
or
Off
modes have been activated via the keypad. If selecting
Hand On
or
Off
, the two timers will be reset to 0, and not start counting until
Auto
is pressed and an active start
command applied.
22-75 Short Cycle Protection
Option: Function:
[0] * Disabled Timer set in par.22-76
Interval between Starts is disabled.
[1] Enabled Timer set in par.22-76
Interval between Starts is enabled.
TR200 Programming Guide 4-191