Operation Keys for local control are found at the bot-
tom of the control panel.
[Hand On]
enables control of the adjustable frequency drive via the GLCP. [Hand On] also starts the motor, and it is now
possible to enter the motor speed data by means of the arrow keys. The key can be selected as Enable [1] or
Disable [0] via par.0-40
[Hand on] Key on LCP.
The following control signals will still be active when [Hand On] is activated:
• [Hand On] - [Off] - [Auto on]
•Reset
• Coasting stop inverse
• Reversing
• Set-up select lsb - Set-up select msb
• Stop command from serial communication
• Quick stop
•DC brake
NOTE: External stop signals activated by means of control signals or a serial bus will override a “start” command
via the keypad.
[Off]
stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par.0-41
[Off] Key on LCP. If
no external stop function is selected and the [Off] key is inactive the motor can only be stopped by disconnecting
the line power supply.
[Auto on]
enables the adjustable frequency drive to be controlled via the control terminals and/or serial communication.
When a start signal is applied on the control terminals and/or the bus, the adjustable frequency drive will start.
The key can be selected as Enable [1] or Disable [0] via par.0-42
[Auto on] Key on LCP.
NOTE: An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand
on] – [Auto on].
[Reset]
is used for resetting the adjustable frequency drive after an alarm (trip). It can be selected as
Enable
[1] or
Disable
[0] via par.0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by holding down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.
3-6 TR200 Programming Guide