24-11 Drive Bypass Delay Time
Range: Function:
0 s* [0 - 600 s] Programmable in 1 s increments. Once the bypass function is activated
in accordance with the setting in par.24-10
Drive Bypass Function, the
bypass delay timer begins to operate. If the adjustable frequency drive
has been set for a number of restart attempts, the timer will continue to
run while the adjustable frequency drive tries to restart. If the motor re-
starts within the time period of the bypass delay timer, then the timer is
reset.
If the motor fails to restart at the end of the bypass delay time, the drive
bypass relay will be activated, which will have been programmed for
Bypass in par.5-40
Function Relay. If a [Relay Delay] has also been pro-
grammed in par.5-41
On Delay, Relay, [Relay] or par.5-42 Off Delay,
Relay, [Relay], then this time must also elapse before the relay action is
performed.
Where no restart attempts are programmed, the timer will run for the
delay period set in this parameter and will then activate the drive bypass
relay, which will have been programmed for Bypass in par.5-40
Function
Relay, Function Relay. If a relay delay has also been programmed in par.
5-41
On Delay, Relay, On Delay, Relay or par.5-42 Off Delay, Relay, [Re-
lay], then this time must also elapse before the relay action is performed.
Parameter Description
4-214 TR200 Programming Guide