Custom Readout
The calculated value to be displayed is based on settings in par.0-30
Custom Readout Unit, par.0-31 Custom
Readout Min Value (linear only), par.0-32 Custom Readout Max Value, par.4-13 Motor Speed High Limit
[RPM], par.4-14 Motor Speed High Limit [Hz] and actual speed.
The relation will depend on the type of unit selected in par.0-30 Custom Readout Unit:
Unit Type
Speed Relation
Dimensionless Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure Quadratic
Power Cubic
0-30 Custom Readout Unit
Option: Function:
Program a value to be shown in the display of the keypad. The value has
a linear, squared or cubed relation to speed. This relation depends on
the unit selected (see table above). The actual calculated value can be
read in par.16-09
Custom Readout, and/or shown in the display by se-
lecting Custom Readout [16-09] in par.0-20
Display Line 1.1 Small to par.
0-24
Display Line 3 Large.
[0]
[1] * %
[5] PPM
[10] min
[11] RPM
[12] PULSE/s
[20] liter / sec.
[21] liter / min
[22] liter / hr.
[23] m³ / sec.
TR200 Programming Guide 4-13