0-45 [Drive Bypass] Key on LCP
Option: Function:
Press [Off] and select Disabled [0] to avoid accidental stop of the drive.
Press [Off] and select Password [2] to avoid unauthorized stop and reset
of the drive. If par.0-45
[Drive Bypass] Key on LCP is included in the quick
menu, define the password in par.0-65
Personal Menu Password.
[0] Disabled No function
[1] * Enabled [Off/Reset] Key is enabled
[2] Password
[3]
[4]
[5]
[6]
Copy parameter settings between set-ups and to/from the keypad.
0-50 LCP Copy
Option: Function:
[0] * No copy No function
[1] All to LCP Copies all parameters in all set-ups from the adjustable frequency drive
memory to the keypad memory. For service purposes, it is recommen-
ded to copy all parameters to the keypad after commissioning.
[2] All from LCP Copies all parameters in all set-ups from the keypad memory to the ad-
justable frequency drive memory.
[3] Size indep. of LCP Copies only the parameters that are independent of the motor size. The
latter selection can be used to program several adjustable frequency
drives with the same function without disturbing motor data which are
already set.
This parameter cannot be adjusted while the motor is running.
4-18 TR200 Programming Guide