EasyManua.ls Logo

Trane TR200 - Page 65

Trane TR200
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-52 Min Speed Normal Magnetizing [Hz]
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load while the
motor is running at low speed, and obtain the optimum U/f characteristic.
The motor size determines the frequency range within which this pa-
rameter is active.
Motor size Change-over
0.3–10 hp [0.25–7.5 kW] < 10 Hz
15–60 hp [11–45 kW] < 5 Hz
75–750 hp [55 kW–550 kW] < 3–4 Hz
1-61 High Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load while the
motor is running at high speed, and obtain the optimum U/f character-
istic. The motor size determines the frequency range within which this
parameter is active.
Motor size Change-over
0.3–10 hp [0.25–7.5 kW] > 10 Hz
15–60 hp [11–45 kW] < 5 Hz
75–750 hp [55 kW–550 kW] < 3–4 Hz