1-52 Min Speed Normal Magnetizing [Hz]
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant]
1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load while the
motor is running at low speed, and obtain the optimum U/f characteristic.
The motor size determines the frequency range within which this pa-
rameter is active.
Motor size Change-over
0.3–10 hp [0.25–7.5 kW] < 10 Hz
15–60 hp [11–45 kW] < 5 Hz
75–750 hp [55 kW–550 kW] < 3–4 Hz
1-61 High Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load while the
motor is running at high speed, and obtain the optimum U/f character-
istic. The motor size determines the frequency range within which this
parameter is active.
Motor size Change-over
0.3–10 hp [0.25–7.5 kW] > 10 Hz
15–60 hp [11–45 kW] < 5 Hz
75–750 hp [55 kW–550 kW] < 3–4 Hz
4-28 TR200 Programming Guide